How is that accomplished in the AirBoss® / 1200 System? |
||
At the end of a Heating and Cooling call, the panel goes into a 3-minute Energy Conservation Cycle. During the first 2 minutes, the dampers are held in place to deliver the residual conditioned air to the last zone(s) that called for it. During the third minute of this cycle, all the dampers open to set up the system for the next call. AirBoss® panels are equipped with an ECC bypass switch. When the switch is in the ECC ON position, it will skip the third minute and either stop the pump with the last zone left open, or move to the next calling zone.
|
||